TPR6 HP PLUS
MV switchgear for primary distribution, SF6-insulated and sealed for life: vacuum circuit breaker, switch-disconnector and disconnector, up to 36 kV, 2000 A and 31.5 kA.
Primary distribution, without gas handling on site
Metal-enclosed MV switchgear, SF6-insulated, factory-assembled and type-tested, maintenance-free. The main devices (vacuum circuit breaker, 3-position switch) are housed in hermetically welded stainless steel tanks; the solid-insulated busbars are outside the gas compartments. No gas work is needed, neither at installation nor for an extension.
built on the experience of the TPR6 series in secondary distribution
up to 2000 A and 31.5 kA, for demanding installations
welded stainless steel tanks, maintenance-free, no gas handling on site
accessible mechanisms outside the gas, cables connected at the front
The product
Construction
Three-pole, metal-enclosed, SF6-insulated MV switchgear, factory-assembled and type-tested, maintenance-free. Available modules: vacuum circuit breaker, switch-disconnector and disconnector.
- Main devices (circuit breaker, 3-position switch) housed in hermetically welded stainless steel tanks: the switchgear is sealed for life.
- Modules connected by solid-insulated busbars located outside the gas compartments.
- No gas work, neither at installation nor for an extension.
- Operating mechanisms (circuit breaker, switch-disconnector and 3-position disconnector) outside the gas compartment, accessible at all times.
- Current and voltage transformers normally outside the gas compartment.
- Cables connected at the front, on a single level, at a convenient mounting height.
Characteristics
- Insulation voltage
- Up to 36 kV
- Rated frequency
- 50 – 60 Hz
- Rated current
- Up to 2000 A
- Rated short-time withstand current Ik
- Up to 31.5 kA
- Rated duration of short circuit tk
- 1 – 3 s
- Degree of protection, front face (indoor)
- IP 3X – 41
- Insulation
- SF6, stainless steel tanks sealed for life
- Breaking
- Vacuum circuit breaker