TPR Air
MV switchgear insulated with dry air, SF6-free. The arc is extinguished in a vacuum interrupter, coordinated with the 3-position switch-disconnector by a patented system.
TPR AIR, the SF6-free RMU
A patented system coordinates the vacuum interrupter and the 3-position switch-disconnector for breaking, closing and earthing. Dry air replaces SF6 as the insulating medium: no greenhouse gas emissions, no toxic decomposition products. Compact LLC and LLT combinations, extensible, ready for remote control.
dry air insulation, global warming potential < 1, no toxic decomposition products
extensible units, small dimensions and reduced weight
live parts in vacuum or in a sealed stainless steel tank, service life > 40 years
remote monitoring, SCADA-ready
The product
Overview
To meet European requirements for emission reduction and decarbonisation, SEL has developed an SF6-free 3-position switch-disconnector. A patented system coordinates the vacuum interrupter and the switch-disconnector for breaking, closing and earthing MV circuits.
This device uses air as the insulating medium: it reduces greenhouse gas emissions and produces no toxic decomposition products during operation.
Construction
- Modular units, extensible for future needs.
- Small dimensions and reduced weight: easier handling, installation and civil works.
- Live parts in vacuum or in a sealed stainless steel tank, maintenance-free.
- IP65 degree of protection for the primary part.
- Indoor version IP3X (up to IP41) and outdoor version IP55, with a lockable front door held open by a gas strut.
- Rated current guaranteed without derating up to 55 °C ambient temperature.
- Connection suited to cables, auxiliaries can be mounted live.
Extensibility
- Extensible version on the left, right or both sides, by busbar coupling.
- Version prepared for future extension.
- Allow at least 150 mm between two switchboards and lateral space for coupling.
Operation
Opening: current first flows through the main contact; as it moves, it briefly connects with the vacuum interrupter contacts without interrupting the current, then separates from them. All the current then flows through the interrupter, whose opening is driven by the patented system: the circuit is open.
Earthing: the switch and the linked circuit can then be earthed by operating the mechanism.
Closing: the mechanism moves the switch from the earthing position to the open position, then closed. The vacuum interrupter plays no part in closing: current flows through the main contacts and the interrupter, closed again, is ready for the next opening.
Vacuum circuit breaker
A new super-compact concept combining disconnector and vacuum circuit breaker: three vacuum interrupters with fault-making and fault-breaking capacity. The outgoing cable is earthed by the circuit breaker in series with the earthing switch.
Options
- Self-powered protection relays (ring core CTs on cables) or relays with power supply, from well-known brands, mounted on the circuit breaker or in an LV compartment (on the roof or at the front, 450 mm high).
- Motorisation of the operating mechanisms (circuit breaker and switch).
- Shunt opening and closing releases, undervoltage release, auxiliary contacts, heater.
- Voltage presence indicator with test point for phase comparison, and HVSensor voltage detector.
- Monitoring and remote control: remote terminal unit, voltage, current, temperature and humidity sensors, Wi-Fi / GSM communication, SCADA-ready solutions.
Safety
- During cable testing, there is no need to break the switchgear earthing system.
- Interlock operated by the earthing switch and additional interlocks against incorrect operations.
- All live parts are contained in a sealed stainless steel tank, suited to harsh environments.
- All operations are carried out from the front with simple devices.
Units
| Code | Function | Width (mm) | Height (mm) | Depth (mm) |
|---|---|---|---|---|
| I | Cable connection | 375 | 1500 | 835 |
| L | Network switch-disconnector | 375 | 1500 | 835 |
| C | 630 A vacuum circuit breaker with disconnector | 450 | 1500 | 835 |
| T | 200 A vacuum circuit breaker with disconnector | 450 | 1500 | 835 |
| M | Metering | 840 | 1500 | 835 |
| M2 | Metering (M2 version) | 840 | 1500 | 835 |
| LC | Switch-disconnector + 630 A vacuum circuit breaker with disconnector | 815 | 1500 | 835 |
| LT | Switch-disconnector + 200 A vacuum circuit breaker with disconnector | 815 | 1500 | 835 |
| LCL | Switch-disconnector + 630 A vacuum circuit breaker with disconnector + switch-disconnector | 1180 | 1500 | 835 |
| LTL | Switch-disconnector + 200 A vacuum circuit breaker with disconnector + switch-disconnector | 1180 | 1500 | 835 |
| LLC | 2 switch-disconnectors + 630 A vacuum circuit breaker with disconnector | 1180 | 1500 | 835 |
| LLT | 2 switch-disconnectors + 200 A vacuum circuit breaker with disconnector | 1180 | 1500 | 835 |
| LCC | Switch-disconnector + 2 × 630 A vacuum circuit breakers with disconnector | 1255 | 1500 | 835 |
| LTT | Switch-disconnector + 2 × 200 A vacuum circuit breakers with disconnector | 1255 | 1500 | 835 |
| LLCC | 2 switch-disconnectors + 2 × 630 A vacuum circuit breakers with disconnector | 1620 | 1500 | 835 |
| LLTT | 2 switch-disconnectors + 2 × 200 A vacuum circuit breakers with disconnector | 1620 | 1500 | 835 |
Single-line diagrams


Characteristics
Common characteristics
| Characteristic | Unit | 12 kV | 17.5 kV | 24 kV |
|---|---|---|---|---|
| Rated voltage | kV | 12 | 17,5 | 24 |
| Rated short-duration power-frequency withstand voltage Ud | kV | 28 | 38 | 50 |
| Rated lightning impulse withstand voltage Up | kV | 75 | 95 | 125 |
| Rated frequency fr | Hz | 50 | ||
| Rated continuous current Ir, busbar | A | 630 | ||
| Rated continuous current Ir, feeders | A | up to 630 | ||
| Rated peak withstand current Ip | kA | up to 52.5 | ||
| Rated short-time withstand current Ik (up to 3 s) | kA | up to 21 | ||
| Insulating medium | Dry air | |||
| Global warming potential | < 1 | |||
| Rated filling level | kPa | 210 | ||
| Ambient air temperature (standard) | °C | −25 to +55 | ||
| Internal arc classification (option) | up to IAC A FLR 21 kA 1 s | |||
| Partition class | PM | |||
| Loss of service continuity | LSC 2 | |||
| Degree of protection | IP65 (primary part) | |||
| Expected service life (normal conditions) | > 40 years | |||
Switching devices
| Characteristic | Unit | Value (12 / 17.5 / 24 kV) |
|---|---|---|
| 3-position switch-disconnector | ||
| Rated mainly active load breaking current Iload | A | 630 |
| Rated short-circuit making current Ima | kA | up to 52.5 |
| Electrical endurance | E3, 100 cycles at Iload, 5 closings at Ima | |
| Capacitive switching | C2 | |
| Mechanical endurance | M1 / 1000 cycles | |
| Vacuum circuit breaker “C” with 3-position disconnector | ||
| Rated mainly active load breaking current Iload | A | 630 |
| Rated operating sequence | O – 0.3 s – CO – 3 min – CO | |
| Rated short-circuit breaking current Isc | kA | up to 21 |
| Electrical endurance | E2, 50 breaks at Isc | |
| Capacitive switching, cable switching | C1, S1 | |
| Mechanical endurance | M2 / 10,000 cycles | |
| Vacuum circuit breaker “T” with 3-position disconnector | ||
| Rated mainly active load breaking current Iload | A | 200 |
| Rated operating sequence | CO – 15 s – CO | |
| Rated short-circuit breaking current Isc | kA | up to 21 |
| Electrical endurance | E2, 50 breaks at Isc | |
| Capacitive switching, cable switching | C1, S1 | |
| Mechanical endurance | M2 / 2000 cycles | |
| Common functions | ||
| Disconnector function, mechanical endurance | M0 / 1000 cycles | |
| Make-proof earthing switch, Ima | kA | up to 52.5 |
| Earthing switch, endurance | E2, 5 closings at Ima, M0 / 1000 cycles | |