Product view 1
1 / 4
SEL TPS, SF6 breaking, air insulation

TPS

Modular MV units with SF6 gas breaking and air insulation, manufactured to IEC 62271-200.

24 kV
Voltage
630 A
Current
12.5 – 16 – 20 kA
Short-time Ik

Air-insulated MV switchgear (AIS)

Hybrid design: SF6 breaking (sealed resin bottle) + air insulation for the busbar, giving direct compatibility with existing equipment and easier maintenance. 9 modular units cover all functions: SM, FS, FIM, 2ICB, ICB, MTA, ACO, SMS, SMH. Compliant with IEC 62271-200.

SF6 breaking, air insulation

sealed resin bottle, busbars and cable boxes in air

Safe, long-lasting operation

no maintenance of the breaking chamber

Compact dimensions

adaptable to existing equipment

Build your switchboard

Choose the units: the single-line diagram and the dimensions update automatically. Then send your composition to our engineering department for a quote.

Start from an example
Add a unit

Recommended order: network incomers (SM) → metering (FIM) → main protection (2ICB) → transformer feeders (FS). Widths calculated with SM, FS and SMH units at 375 mm (they also exist in 500 mm).

Unit SM : Modular incoming switch unit
SM
Unit SM : Modular incoming switch unit
SM
Unit FIM : Modular voltage metering unit with disconnector
FIM
Unit 2ICB : Main protection
2ICB
Unit FS : Modular fuse protection unit
FS
Unit FS : Modular fuse protection unit
FS

Top of the list: left side of the switchboard.

  1. SMIncoming switch
  2. SMIncoming switch
  3. FIMVoltage metering
  4. 2ICBMain protection
  5. FSFuse protection
  6. FSFuse protection
SMSMFIM2ICBFSFS
Units
6
Total width
2,750 mm
Height
1600 mm
Depth
840 mm

Indicative dimensions, calculated from the width of each unit. Our engineering department validates the composition and equipment with you.

Request a quote for this composition
Quote

The product

Architecture

Design

The TPS range is built in a metal frame made of assembled galvanised sheet panels. The assembled structure gives the unit resistance to mechanical impacts and electrodynamic stresses. Breaking takes place in a sealed resin bottle filled with SF6, and insulation is in air (busbars and cable boxes).

The main advantages of the TPS are shorter installation and maintenance times and a compact footprint, while maintaining a high level of operator safety.

Functions

Vacuum circuit breaker

The ICB (circuit breaker) and 2ICB (main protection) units are fitted with a TCB-type vacuum circuit breaker, with the operating sequence O – 0.3 s – CO – 3 min – CO.

  • Protection relay, current transformers and undervoltage release.
  • Optional: circuit breaker motorisation, shunt opening and/or closing release, auxiliary contacts.
Safety

Safety

Personnel safety is ensured by mechanical interlocks performing the following functions:

  • Closing the line switch locks the operation of the earthing switch and the opening of the access door.
  • Closing the earthing switch prevents closing the line switch but allows the access door to be opened.
  • Opening the access door allows the earthing switch to be opened for testing incoming or outgoing cables, but never the closing of the line switch.
  • A key system secures the interlocking between the transformer protection units and the LV circuit breaker.

Units

CodeFunctionWidth (mm)Height (mm)Depth (mm)
SMModular incoming switch unit375 / 5001600840
FSModular fuse protection unit375 / 5001600840
FIMModular voltage metering unit with disconnector5001600840
2ICBMain protection7501600840
ICBModular circuit breaker unit7501600840
MTABusbar riser with metering current transformer5001600840
ACONormal / standby unit7501600840
SMSModular surge arrester unit3751600840
SMHEarth fault feeder unit375 / 5001600840

Single-line diagrams

SM375 / 500 mm
Single-line diagram of unit SM
Modular incoming switch unit
FS375 / 500 mm
Single-line diagram of unit FS
Modular fuse protection unit
FIM500 mm
Single-line diagram of unit FIM
Modular voltage metering unit with disconnector
2ICB750 mm
Single-line diagram of unit 2ICB
Main protection
ICB750 mm
Single-line diagram of unit ICB
Modular circuit breaker unit
MTA500 mm
Single-line diagram of unit MTA
Busbar riser with metering current transformer
ACO750 mm
Single-line diagram of unit ACO
Normal / standby unit
SMS375 mm
Single-line diagram of unit SMS
Modular surge arrester unit
SMH375 / 500 mm
Single-line diagram of unit SMH
Earth fault feeder unit

Characteristics

Rated voltageUnit24 kV36 kV
Altitudem≤ 1000
Ambient temperature°C−5 to 40
Humidity%95
Insulation voltagekV2436
Rated voltagekV2436
Rated withstand voltage phase-to-earthkV125170
Rated withstand voltage across the isolating distancekV145195
Power-frequency withstand voltage on main circuits between phaseskV5075
Power-frequency withstand voltage on main circuits across the isolating distancekV6080
FrequencyHz50 – 60
Rated currentA630
Short-time current IkkA12,5 – 16 – 2012,5 – 16 – 20
Peak short-time current Ip (making capacity)kA2.5 × Ik
Short-circuit withstand time Iks3
Degree of protection, external partIP3X
Degree of protection, internal partIP20
Mechanical endurance, switch-disconnector1000 operations / class M1
Electrical endurance, switch-disconnector100 breaks at Inpf = 0.7 / class E3
Mechanical endurance, earthing switch IEC 62271-1021000 operations / class M1
Electrical endurance, earthing switch IEC 62271-1025 closings / class E2
Mechanical endurance, circuit breaker IEC 62271-100 module C/P/D10,000 operations / M2
Electrical endurance, circuit breaker IEC 62271-100 module C/P/DE2
Mechanical endurance, circuit breaker IEC 62271-100 module T2000 operations / M1
Electrical endurance, circuit breaker IEC 62271-100 module TE1
Rated operating sequenceO – 0.3 s – CO – 3 min – CO
Internal arc withstand currentkA s16 kA 1 s