TPR6 modular
The MV delivery substation, built unit by unit. Network incomers, MV metering, main protection with double isolation and transformer feeders: each function is an independent SF6-insulated unit sealed for life, up to 24 kV.
each function has its own SF6 tank sealed for life
N, R and U units for delivery substations
circuit breaker between the R and U units
a unit can be added without touching the others
Build your switchboard
Choose the units and the side of the network incomers: the single-line diagram and the dimensions update automatically. Then send your composition to our engineering department for a quote.
Recommended order: network incomers (L) → metering (N) → main protection (R + U) → transformer feeders (F, C or T). The main protection always combines the R and U units.
Top of the list: left side of the switchboard.
- LIncoming / outgoing
- LIncoming / outgoing
- NMetering
- R UMain protection
- FTransformer by fuses
- FTransformer by fuses
- Units
- 7
- Total width
- 3,710 mm
- Height
- 1470 mm
- Depth
- 717 mm
Indicative dimensions, calculated from the width of each unit. Our engineering department validates the composition and equipment with you.
The product
Modular construction
Each unit is an independent unit, with its own stainless steel tank filled with SF6 and sealed for life. The units are placed side by side and connected by their busbar to form the switchgear: an LLNRUFF substation has 7 separate units. The exact substation diagram can be built, a unit can be added later without touching the others, and one unit has no effect on the insulation of its neighbours.
Design
The stainless steel enclosure, leak-tight and sealed for life, houses the live parts of each unit. Insulation and breaking take place in SF6, whose dielectric strength, much higher than that of air, extinguishes the arc instantly.
- Long service life.
- No maintenance on the switching devices.
- Reliable operation.
- Compact dimensions.
Unit order
The switchgear follows the path of the energy: network incomers (L) → metering (N) → main protection (R + U) → transformer feeders (F, C or T). It is built with the incomers on the left (LLNRUFF) or on the right (FFURLNLL). In the latter case, the main protection unit is fitted in its mirror version, RL.
Main protection with double isolation (R + U units)
The substation's main protection combines two adjacent units. The R unit carries the 630 A circuit breaker and its protection relay. The U unit, a busbar riser fitted with a switch, is placed right after it, on the feeder side.
The circuit breaker is thus framed by two isolating devices: that of the R unit on the network side, and the switch of the U unit on the feeder side. It can be isolated on both sides and then earthed for safe work. This is the double isolation of the main protection. Since the switching devices are enclosed in SF6 gas, the position of each device is shown on the front mimic diagram.
MV metering (N unit)
The N unit houses the metering voltage transformers, protected by 24 kV 0.5 A fuses. Current transformers for metering or measurement can be added as an option.
3-position switch
The switch-disconnector has three positions: closed (A), open (B) and earthed (C). For safe operation, its position is mechanically interlocked with the earthing position.
Personnel safety
Mechanical interlocks enforce the correct operating sequence (F, C and T units):
- Switch closed: earthing and opening the cable access door are impossible.
- Earthing in place: closing onto the line is impossible, the cable access door can be opened.
- Door open: the earthing position cannot be left.
- All three positions can be padlocked.
Internal arc and pressure gauge
The metal structure withstands an internal fault and protects the operator. In the event of an arc, a safety valve at the bottom releases the gases downwards, away from the operator and nearby equipment. A pressure gauge continuously shows the condition of the SF6 gas.
Units
| Code | Function | Width (mm) | Height (mm) | Depth (mm) |
|---|---|---|---|---|
| L | Switch-disconnector | 390 | 1470 | 717 |
| F | Transformer protection, switch-fuse combination | 390 | 1470 | 717 |
| N | MV metering | 840 | 1470 | 717 |
| R | Main protection, 630 A circuit breaker (with U: double isolation) | 840 | 1470 | 717 |
| RL | Main protection, mirror version of R (incomers on the right) | 840 | 1470 | 717 |
| U | Busbar riser with switch, second isolation of the main protection | 470 | 1470 | 717 |
| C | Transformer protection by 630 A circuit breaker | 470 | 1470 | 717 |
| T | Transformer protection by 200 A circuit breaker | 470 | 1470 | 717 |
| I | Cable riser | 390 | 1470 | 717 |
Characteristics
- Rated voltage
- 24 kV
- Lightning impulse withstand voltage
- 125 kV, 145 kV across the isolating distance
- Power-frequency withstand voltage
- 50 kV, 60 kV across the isolating distance
- Frequency
- 50 – 60 Hz
- Rated current
- 630 A
- Rated short-time withstand current Ik
- Up to 25 kA 1 s
- Peak current Ip
- 2.5 × Ik
- Internal arc withstand
- 16 kA 1 s
- Unit dimensions
- Width 390, 470 or 840 mm, height 1470 mm, depth 717 mm
- Degree of protection
- IP 3X enclosure, IP 67 MV circuits
- Switch-disconnector
- M1, 1000 operations, E3, 100 breaks
- Earthing switch
- M1, 1000 operations, E2, 5 closings
- 630 A circuit breaker (R and C units)
- M2, 10,000 operations, E2
- 200 A circuit breaker (T unit)
- M1, 2000 operations, E1
- Circuit breaker operating sequence
- O – 0.3 s – CO – 3 min – CO
- Service conditions
- −25 to +55 °C, humidity 95 %, altitude ≤ 1000 m