TPR6 630 A
Compact SF6-insulated MV switchgear, sealed for life and extensible, for secondary distribution substations up to 24 kV. It combines switch-disconnectors and transformer protection by fuses or circuit breaker in a maintenance-free stainless steel enclosure.
stainless steel tank, live parts protected from humidity, dust and pollution
insulation and breaking in SF6, long service life
on the right or on both sides, without replacing the installed switchgear
transformer protection by fuses, 200 A or 630 A circuit breaker
The product
Overview
The TPR6 630 A is a compact switchgear (RMU) of the TPR6 range. It performs all the switching operations of a secondary distribution substation: ring incoming and outgoing feeders, transformer protection by fuses or circuit breaker. It is manufactured to IEC 62271-200.
Design
The stainless steel enclosure, leak-tight and sealed for life, houses all the live parts and the busbar. Insulation and breaking take place in SF6, whose dielectric strength, much higher than that of air, extinguishes the arc instantly.
- Long service life.
- No maintenance on the switching devices.
- Reliable operation.
- Compact dimensions.
Extensibility
All compositions are extensible, on the right or on both sides: one or more elements can be added to the existing switchgear with suitable connectors, without replacing it.
Cable connection and testing
Cables are connected by bolted T-connectors on type C 630 A bushings (standardised EN 50181 interface). Cable testing is done directly at the connections, using suitable T-connectors.
Front panel and operation
Controls, the live mimic diagram and the voltage presence indicators are grouped on the front panel. Switches are operated by spring mechanisms; the mimic diagram shows their position. Fuses and the cable compartment are accessible through a front door interlocked with the earthing switch. An LV compartment can be added above the switchgear.
3-position switch
The switch-disconnector has three positions: closed (A), open (B) and earthed (C). For safe operation, its position is mechanically interlocked with the earthing position.
Personnel safety
Mechanical interlocks enforce the correct operating sequence (F, C and T units):
- Switch closed: earthing and opening the cable access door are impossible.
- Earthing in place: closing onto the line is impossible, the cable access door can be opened.
- Door open: the earthing position cannot be left.
- All three positions can be padlocked.
Internal arc and pressure gauge
The metal structure withstands an internal fault and protects the operator. In the event of an arc, a safety valve at the bottom releases the gases downwards, away from the operator and nearby equipment. A pressure gauge continuously shows the condition of the SF6 gas.
Units
| Code | Function | Width (mm) | Height (mm) | Depth (mm) |
|---|---|---|---|---|
| L | Switch-disconnector | 350 | 1470 | 675 |
| F | Transformer protection, switch-fuse combination | 350 | 1470 | 675 |
| C | Transformer protection by 630 A circuit breaker | 350 | 1470 | 675 |
| T | Transformer protection by 200 A circuit breaker | 350 | 1470 | 675 |
Single-block compositions
Extensible switchgear. All TPR6 630 A compositions are extensible, on the right or on both sides: units can be added later without replacing the installed switchgear. The + sign shows the extensible side: LLF+ is extensible on the right, +LLF+ on the right and left.
Characteristics
- Rated voltage
- 24 kV
- Lightning impulse withstand voltage
- 125 kV, 145 kV across the isolating distance
- Power-frequency withstand voltage
- 50 kV, 60 kV across the isolating distance
- Frequency
- 50 – 60 Hz
- Rated current
- 630 A
- Rated short-time withstand current Ik
- Up to 25 kA, 1 to 3 s
- Peak current Ip
- 2.5 × Ik
- Internal arc withstand
- 16 kA 1 s
- Cable connection
- Type C 630 A bushings (EN 50181)
- Degree of protection
- IP 3X enclosure, IP 67 MV circuits
- Switch-disconnector
- M1, 1000 operations, E3, 100 breaks
- Earthing switch
- M1, 1000 operations, E2, 5 closings
- 630 A circuit breaker (C unit)
- M2, 10,000 operations, E2
- 200 A circuit breaker (T unit)
- M1, 2000 operations, E1
- Circuit breaker operating sequence
- O – 0.3 s – CO – 3 min – CO
- Service conditions
- −25 to +55 °C, humidity 95 %, altitude ≤ 1000 m