Product view 1
1 / 3
TPR6 400 A

TPR6 400 A

Compact SF6-insulated MV switchgear, sealed for life, for secondary distribution substations up to 24 kV. Single-block and ready to connect, it combines switch-disconnectors and fuse transformer protection in a maintenance-free stainless steel enclosure.

24 kV
Voltage
400 A
Current
16 kA 1 s
Short-time Ik
Sealed for life

stainless steel tank, live parts protected from humidity, dust and pollution

Maintenance-free

insulation and breaking in SF6, long service life

Compact

up to 5 functions in a width of 1790 mm

Type B 400 A bushings

cable testing through bushings at the top of the incoming units

The product

Architecture

Overview

The TPR6 400 A is a compact switchgear (RMU) of the TPR6 range. It performs all the switching operations of a secondary distribution substation: ring incoming and outgoing feeders, transformer protection by fuses. It is manufactured to IEC 62271-200.

Design

The stainless steel enclosure, leak-tight and sealed for life, houses all the live parts and the busbar. Insulation and breaking take place in SF6, whose dielectric strength, much higher than that of air, extinguishes the arc instantly.

  • Long service life.
  • No maintenance on the switching devices.
  • Reliable operation.
  • Compact dimensions.

Cable connection and testing

Cables are connected by plug-in connectors on type B 400 A bushings (standardised EN 50181 interface). On the L incoming units, cable testing is done through bushings located at the top of the unit, accessible from the front, without removing the connections.

Cable test bushings at the top of the TPR6 400 A incoming units
Functions

Front panel and operation

Controls, the live mimic diagram and the voltage presence indicators are grouped on the front panel. Switches are operated by spring mechanisms; the mimic diagram shows their position. Fuses and the cable compartment are accessible through a front door interlocked with the earthing switch. An LV compartment can be added above the switchgear.

3-position switch

The switch-disconnector has three positions: closed (A), open (B) and earthed (C). For safe operation, its position is mechanically interlocked with the earthing position.

3-position switch: (A) closed, (B) open, (C) earthed
Safety

Personnel safety

Mechanical interlocks enforce the correct operating sequence (F unit):

  • Switch closed: earthing and opening the cable access door are impossible.
  • Earthing in place: closing onto the line is impossible, the cable access door can be opened.
  • Door open: the earthing position cannot be left.
  • All three positions can be padlocked.

Internal arc and pressure gauge

The metal structure withstands an internal fault and protects the operator. In the event of an arc, a safety valve at the bottom releases the gases downwards, away from the operator and nearby equipment. A pressure gauge continuously shows the condition of the SF6 gas.

Units

CodeFunctionWidth (mm)Height (mm)Depth (mm)
LSwitch-disconnector3501470675
FTransformer protection, switch-fuse combination3501470675

Single-block compositions

Height
1470 mm
Depth (without rear access)
675 mm
Depth (with rear access)
720 mm
Width
1090mm
1 configuration
Width
1440mm
2 configurations
Width
1790mm
2 configurations

Characteristics

Rated voltage
24 kV
Lightning impulse withstand voltage
125 kV, 145 kV across the isolating distance
Power-frequency withstand voltage
50 kV, 60 kV across the isolating distance
Frequency
50 – 60 Hz
Rated current
400 A
Rated short-time withstand current Ik
16 kA 1 s
Peak current Ip
2.5 × Ik (40 kA)
Internal arc withstand
16 kA 1 s
Cable connection
Type B 400 A bushings (EN 50181)
Degree of protection
IP 3X enclosure, IP 67 MV circuits
Switch-disconnector
M1, 1000 operations, E3, 100 breaks
Earthing switch
M1, 1000 operations, E2, 5 closings
Service conditions
−25 to +55 °C, humidity 95 %, altitude ≤ 1000 m