TPR6 400 A
Compact SF6-insulated MV switchgear, sealed for life, for secondary distribution substations up to 24 kV. Single-block and ready to connect, it combines switch-disconnectors and fuse transformer protection in a maintenance-free stainless steel enclosure.
stainless steel tank, live parts protected from humidity, dust and pollution
insulation and breaking in SF6, long service life
up to 5 functions in a width of 1790 mm
cable testing through bushings at the top of the incoming units
The product
Overview
The TPR6 400 A is a compact switchgear (RMU) of the TPR6 range. It performs all the switching operations of a secondary distribution substation: ring incoming and outgoing feeders, transformer protection by fuses. It is manufactured to IEC 62271-200.
Design
The stainless steel enclosure, leak-tight and sealed for life, houses all the live parts and the busbar. Insulation and breaking take place in SF6, whose dielectric strength, much higher than that of air, extinguishes the arc instantly.
- Long service life.
- No maintenance on the switching devices.
- Reliable operation.
- Compact dimensions.
Cable connection and testing
Cables are connected by plug-in connectors on type B 400 A bushings (standardised EN 50181 interface). On the L incoming units, cable testing is done through bushings located at the top of the unit, accessible from the front, without removing the connections.

Front panel and operation
Controls, the live mimic diagram and the voltage presence indicators are grouped on the front panel. Switches are operated by spring mechanisms; the mimic diagram shows their position. Fuses and the cable compartment are accessible through a front door interlocked with the earthing switch. An LV compartment can be added above the switchgear.
3-position switch
The switch-disconnector has three positions: closed (A), open (B) and earthed (C). For safe operation, its position is mechanically interlocked with the earthing position.
Personnel safety
Mechanical interlocks enforce the correct operating sequence (F unit):
- Switch closed: earthing and opening the cable access door are impossible.
- Earthing in place: closing onto the line is impossible, the cable access door can be opened.
- Door open: the earthing position cannot be left.
- All three positions can be padlocked.
Internal arc and pressure gauge
The metal structure withstands an internal fault and protects the operator. In the event of an arc, a safety valve at the bottom releases the gases downwards, away from the operator and nearby equipment. A pressure gauge continuously shows the condition of the SF6 gas.
Units
| Code | Function | Width (mm) | Height (mm) | Depth (mm) |
|---|---|---|---|---|
| L | Switch-disconnector | 350 | 1470 | 675 |
| F | Transformer protection, switch-fuse combination | 350 | 1470 | 675 |
Single-block compositions
Characteristics
- Rated voltage
- 24 kV
- Lightning impulse withstand voltage
- 125 kV, 145 kV across the isolating distance
- Power-frequency withstand voltage
- 50 kV, 60 kV across the isolating distance
- Frequency
- 50 – 60 Hz
- Rated current
- 400 A
- Rated short-time withstand current Ik
- 16 kA 1 s
- Peak current Ip
- 2.5 × Ik (40 kA)
- Internal arc withstand
- 16 kA 1 s
- Cable connection
- Type B 400 A bushings (EN 50181)
- Degree of protection
- IP 3X enclosure, IP 67 MV circuits
- Switch-disconnector
- M1, 1000 operations, E3, 100 breaks
- Earthing switch
- M1, 1000 operations, E2, 5 closings
- Service conditions
- −25 to +55 °C, humidity 95 %, altitude ≤ 1000 m